Thin Slab over Frame Floor Applications
• Most thin slab applications are installed during the initial construction
of a building, due to the increased structural requirements to carry the
added weight.
• Lightweight concrete products will increase the floor height by a
minimum of 1.5" (38.1 mm) and the floor load anywhere between
12 to 18 lbs/sq.ft (5.44 k to 8.16 k).
• Theincreaseinloadusuallymeansamodicationtothejoistsystem
and/or other supports.
• Verify a floor’s ability to withstand these loads prior to installing a
lightweight concrete product.
Tube Spacing
• Residential thin slabs will use 6" (152.4 mm), 9" (228.6 mm), or
12" (304.8 mm) tube spacing with some perimeter banding. Banding
is any area where the tubing is installed with a tighter on center
spacing. Usually seen along exterior walls with higher than normal
heat loss.
• Tubing is generally attached directly to the subfloor with the use of
staples and/or NailTites.
Fasteners
The sub-material the thin slab is installed over will determine how
the tubing can be attached. The most common sub-material is a
wooden subfloor.
• Staples—spacedevery18"-24"(457.2mm-609.6mm)oncenter.
Use a staple gun set to 100 psi.
Thin slab Profile
• It is important to maintain at least 3/4" (19.1 mm) of thin slab material
above the tubing.
• More coverage may be necessary depending on the structural
requirements of the slab/structure.
Installation Steps
Manifoldlocations,nalconcretethickness,andzoningdetailsarejust
a few items that can affect how a thin slab application is installed. The
following guidelines cover the most common installation conditions. If
a given situation is not covered here, or if unexpected circumstances
arise, please contact Watts or a heating professional.
1. Install Manifolds
Locate where the manifolds are to be placed.
• With the use of Watts manifold brackets or manifold mounting
enclosure, secure the manifolds to the wall.
• Allowances may need to be made to allow the tubing to transfer
through the wall base plate and into the thin slab.
• Follow local code guidelines when penetrating framing base plates.
12" max
(304.8 mm)
Thin Slab Over Framed Cross Section
Thin Slab Tube Spacing
Thin Slab - Manifold Installation Detail
ThinSlab
SubFloor
Heating PEX or
Heating
PEX-AL-PEX
Insulation
Floor Covering
Mimimum 1-1/2"
(38.1mm)ThinSlab
Insulation
Manifold
ThinSlab
Heating PEX or
Heating
PEX-AL-PEX
Note: Local building or plumbing codes may require
modifications to the information provided. You
are required to consult the local building and
plumbing codes prior to installation. If this
information is not consistent with local building
or plumbing codes, the local codes should
be followed.