Inspect the kit to verify the following parts are present before proceeding with the installation. Contact Hamilton at
1-800-879-0123
if a part is missing.
Read the instructions completely before installing.
The female end of each Z-Vent III component incorporates a silicone sealing gasket (except for 12" Appliance Vent
Adapter).
Examine all components to insure that gasket integrity has remained during shipping. Gaskets must be in
the proper positions or flue gases could leak resulting in carbon monoxide poisoning.
Please Note:
The connection of the 12" Appliance Vent Adapter to the Garage Heater Vent Pipe Connector requires
a continuous bead of Z-Vent high temperature silicone (included) applied to the flange of the Vent Pipe Connector
prior to attaching the Appliance Vent Adapter and tightening Locking Band. (See Illustration on Page 5.)
1. Align pipes and push them together as far as they will go (at least 1.75 inches).
2. Tighten Locking Bands and Gear Clamp to a minimum torque of 40 in/lbs. and maximum of 50 in/lbs.
1"
25mm
1"
25mm
JOINT PROCEDURE
VerticalHorizontal Vertical
CLEARANCE TO COMBUSTIBLES
Clearance
Unenclosed
Horizontal
KIT CONTENTS
1" (25mm)300 F (149 C)
Temperature
Clearance
4" (200mm)
System Operating
1" (25mm)
Enclosed
8" (200mm)
8"
200mm
4"
200mm
3' Vent Pipe
TO GARAGE HEATER
ILLUSTRATION #1
JOINT DETAIL
Screened Vent
Termination Tee
480 F
249 C
Vent Adapter
12" Appliance
FEMALE END
MALE END
LOCKING BAND
3" Gear Clamp
3" Gear Clamp
Adjustable
Wall Thimble