POSSIBLE CAUSES
1. Air inlet disc stuck to seat.
2. “Old Style” pressure vacuum breaker (non-loaded air
inlet valve).
1. Leaking No. 1 shut-off valve.
2. Parallel installation with leaky No. 2 shut-off valve.
1. Dirty or damaged air inlet disc.
2. Scale buildup on seat.
1. Dirty or damaged air inlet disc.
2. Damaged seat.
IS720A (REV. 4/13)
1. Close inlet and outlet shut-off valves before disassembling device.
2. Remove canopy screws counterclockwise and remove canopy.
3. Bleed off pressure by opening the No. 2 test cock.
4. Unscrew the bonnet from the body by turning counterclockwise.
5. Remove the disc & poppet assembly, check spring and spider assembly from body.
6. Clean all parts with clean water only.
7. After completing inspection, replace necessary parts and reassemble. Repair kits are available from your supplier.
8. Retest according to "TEST PROCEDURES".
TEST NO. 1
Purpose: To test the opening pressure dif-
ferential of the air inlet valve.
Requirement: The air inlet valve shall open
when the pressure in the body is no less than
1.0 psi above atmospheric pressure. The air
inlet valve shall be fully open when the water
drains from the body.
STEPS:
1. Bleed water through both test cocks
to eliminate foreign material.
2. Install appropriate ttings for test kit
hoses.
3. Remove air inlet valve canopy.
4. Install the high side hose of the differ-
ential pressure gauge to test cock #2.
Open test cock #2 and bleed air from
hose and gauge.
5. Close #2 shut-off valve then close #1
shut-off valve.
6. Slowly open the high side bleed needle
valve being especially careful not to
drop the pressure differential too fast.
Record the pressure differential at which
the air inlet valve opens.
7. Close test cock #2 and remove equip-
ment.
8. Open #1 shut-off valve.
TEST NO. 2
Purpose: To test the check valve for tightness
in the direction of ow.
Requirement: The check valve shall be drip-
tight in the normal direction of ow when the
inlet pressure is 1.0 psi and the outlet pres-
sure is atmospheric.
STEPS:
1. Attach high side hose of differential
gauge to test cock #1. Open test cock
#1 and bleed all air from the hose and
the gauge by opening high side bleed
needle valve. Close high side bleed
needle valve.
2. Close #1 shut-off valve.
3. Open test cock #2. The air inlet valve
will open and the water in the body will
drain out through test cock #2.
When this ow of water stops, the dif-
ferential pressure indicated by the
gauge after it has settled will be the
pressure drop across the check valve.
This value must be 1.0 psi or greater.
Record this value. If water continues
to ow out of test cock #2, then the #1
shut-off valve is leaking.
4. Close test cocks #1 and #2 and remove
equipment.
5. Replace air inlet valve canopy.
6. Open #1 shut-off valve, then #2 shut-
off valve.
CANOPY
PLASTIC
WASHER
DISC &
POPPET ASSY
SPIDER
ASSY
CANOPY
SCREW
BONNET
O-RING
SPRING
TEST COCK#2
BODY
BALL VALVE
TEST COCK#1
BALL VALVE
PROBLEM
Air inlet valve does not open as gauge drops to 0.0 psid.
Air inlet valve does not open and differential on gauge will
not drop.
Air inlet opens below 1.0 psid.
Check valve opens below 1.0 psid.
Troubleshooting
Testing Procedures
Maintenance
2
ZURN WILKINS
1747 Commerce Way, Paso Robles, CA 93446 Phone:855-663-9876 Fax:805-238-5766
®
www.zurn.com